3.1. Device Object:
The Device object default property values are as follows –
Property Name Default Values
object-identier 7
object-name Device,1
object-type Device
system-status operational
vendor-name ONICON, Incorporated
vendor-identier 206
model-name Vortex Meter
rmware-revision N/A
application-softwareversion 1.07
protocol-version 1
protocol-revision 4
protocol-servicessupported {F,F,F,F,F,F,F,F,F,F,F,F,T,F,T,T,T,T,F,F,F,F,F,F,F,F,F,F,F,F,T,T,F,F,F,F,F}
protocol-object-types-supported {T,F,F,T,F,T,F,F,T,F,F,F,F,F,F,F,F,F,F,F,F,F,F,F,F}
object-list {(analog-input,1), (analog-input,2), (analog-input,3), (analog-
input,4), (analog-input,5), (analog-input,6), (analog-input,7), (analog-
input,8) (analog-input,9), (analog-input,10), (analog-input,11),
(analoginput,12), (analog-input,13), (analog-input,14), (analoginput,
15), (analog-input,16), (analog-input,17), (analoginput, 18), (analog-
input,19), (binary-input,1), (binary-input,2), (binaryinput,3), (binary-
input,4), (binary-value,1), (device,7) }
max-apdu-lengthaccepted 300
segmentation-supported no-segmentation
apdu-timeout 3000
number-of-APDU-retries 1
max-master 127
max-info-frames 1
device-address-binding ()
database-revision 0
Note - Device Communication Control: Password – “vortek”
4.3.3.2. Analog Input Object:
Vortex Mass Flow Meters Analog Input type objects are described
in the below Table –
Object Instance Object Name Unit Description
1 Volume Flow cubic-feet-per-second, cubic-feet-per-
minute, us-gallons-per-minute, imperial-
gallons-perminute, liters-per-minute,
liters-per-second, liters-per-hour, cubic-
meters-per-second, cubic-meters-per-
minute, cubic-meters-per-hour
This AI object is used to
measure volume ow.
Comentários a estes Manuais