F-2600 & F-2700 Vortex Flow Meter Manual 02/15 - 0808-7 / 19204 Page 88
Examples
Read the exception status byte from the device with address 1:
01 07 41 E2
01 Device address
07 Function code, 04 = read exception status
A typical response from the device is as follows:
01 07 03 62 31
01 Device address
07 Function code
03 Exception status byte
62 31 CRC
Request the rst 12 registers from device with address 1:
01 04 00 00 00 0C F0 0F
01 Device address
04 Function code, 04 = read input register
00 00 Starting address
00 0C Number of registers = 12
F0 0F CRC
A typical response from the device is as follows: *Note these are the older register denitions.
01 04 18 00 00 03 E8 00 00 7A 02 6C 62 00 00 41 BA 87 F2 3E BF FC 6F 42 12
EC 8B 4D D1
01 Device address
04 Function code
18 Number of data bytes = 24
00 00 03 E8 Serial number = 1000 (unsigned long)
00 00 7A 02 Totalizer = 31234 lbm (unsigned long)
6C 62 00 00 Totalizer units = “lb” (string, unused characters are 0)
41 BA 87 F2 Mass ow rate = 23.3164 lbm/sec (oat)
3E BF FC 6F Volume ow rate = 0.3750 ft3/sec (oat)
42 12 EC 8B Pressure = 36.731 psia (oat)
4D D1 CRC
An attempt to read register(s) that don’t exist:
01 04 00 00 00 50 F1 D2
01 Device address
04 Function code 4 = read input register
00 00 Starting address
00 50 Number of registers = 80
F0 36 CRC