4.4 START-UP AND COMMISSIONING WORKSHEET
Please read all installation instructions carefully prior to proceeding with these steps. Use the
following worksheet for checking off the commissioning steps and recording measured values.
STEP TEST/MEASUREMENT S/N: _________ S/N: ________ S/N: ________ S/N: _________
1.
Meter location:
2.
Control system programming:
3.
Match display or Btu meter
serial # (S/N) if ordered:
4.
Signal connections veried:
5.
Supply voltage veried:
6.
Connect power:
The following steps require ow in the pipe. Flow signal readings should be taken while holding
the ow rate constant if possible. Otherwise, take the various output readings as quickly as possible.
10.
Analog or binary outputs
4-20 mA signal: ________ mA ________ mA ________ mA ________ mA
scaled output interval ___________ ___________ ___________ ___________
Calculated ow rate: _______ GPM _______ GPM _______ GPM _______ GPM
11
Flow rates displayed on
meter display:
_______ GPM _______ GPM _______ GPM _______ GPM
control system:
_______ GPM _______ GPM _______ GPM _______ GPM
4.5 TROUBLESHOOTING GUIDE
NOTE: Also refer to the START-UP AND COMMISSIONING GUIDE located on the preceeding
pages.
REPORTED PROBLEM POSSIBLE SOLUTIONS
No signal • Verify correct wiring to control system (See wiring diagram.)
• Check display for alarm messages. Verify that the pipe is full.
• Verify that the sensor body and transmitter are both connected to earth ground.
Reading is too high or low • Verify correct wiring to control system (see wiring diagram).
• Conrm that the output signals are consistent (frequency vs. analog, etc).
• Conrm that the control system is programmed for correct ow range or scale factor.
Analog signal seems high or
low and does not correspond
to frequency output
Check for ground loop or offset voltage:
• Verify that the sensor body and transmitter are both connected to earth ground.
• Disconnect analog signal input from control system and measure analog outputs directly from
the ow meter.
• Re-connect signal input to control system and measure the analog signals again.
• Any difference between these readings indicates a potential ground loop or offset voltage.
• Please contact ONICON for further assistance.
Control system displays
ow rate, but no ow rate is
indicated on the local
display module or Btu meter
• Verify that all of the wires from the ow meter are connected to the display module or Btu
meter.
• The frequency output wire (green) must be connected for any ONICON display or Btu meter.