[email protected]D-100 Flow Display Manual 10/14 - 0634-14 / 18340 Page 17
* 4-20mA +
* 24 VDC Supply +
F-5100 Flow Meter
Connections
Connections shown with * are required for
all installations.
* Supply Common -
Flow Meter Inputs
* Shield
* Earth
Inputs & Outputs
Terminal #
* + 24V
* 4-20mA
B5
C5
* - Common B6
* Earth
L1 N Not Used
CAUTION
Shield and earth connections are required for proper operation. Failure to use shielded cable
or to connect earth to both the ow meter and D-100 may result in erratic operation. Shields
should be terminated at the D-100 shield terminals and left unterminated at the ow meter.
3.3.1.7 ONICON F-5100 Series Flow Meters