D-100 Flow Display Manual 10/14 - 0634-14 / 18340 Page 14
* 4-20mA -
* 4-20mA +
F-2000 Flow Meter
Connections
(A) Scaled +
(A) Scaled -
Flow Meter Inputs
* Shield
Auxiliary Flow Meter Signals
* Earth
Outputs Terminal #
* + 24V
* - ILoop
+ 24V
- Pout
* Earth
Connections shown with * are required for all installations. Connections shown with (A) are optional.
1
2
3
4
L1 N Not Used
CAUTION
Shield and earth connections are required for proper operation. Failure to use shielded cable
or to connect earth to both the ow meter and D-100 may result in erratic operation. Shields
should be terminated at the D-100 shield terminals and left unterminated at the ow meter.
!
3.3.1.4 ONICON F-2500 Flow Meters
F-2500 Flow Meter
Connections