STEP ACTION REACTION COMMENT
9
Once the correct value has been
entered, press PROGRAM.
The P1 APP No page will
appear with the rst digit of
the address ashing.
Do not change the P1
app number without rst
consulting ONICON.
10 Press the PROGRAM button.
The FM LOCN page appears
with UNKNWN defaulted as
the current location.
The PROGRAM button is on
the front panel.
11 Press the SCROLL button.
The setting will toggle be-
tween UNKNWN, SUPPLY,
and RETURN.
Select the appropriate FM
LOCN.
12 Press the PROGRAM button.
The FRONT PANEL RESET
page appears.
Do not change this setting
unless you wish to enable
the front panel totalizer reset
button.
13 Press the PROGRAM button.
The SAVE CHANGES page
appears.
The new settings must be
saved to take effect.
14 Press the SCROLL button.
The N changes to Y on the
SAVE CHANGES page.
The Y must be selected in
order for the new settings to
take effect.
15 Press the PROGRAM button.
The new settings are saved
and the display reverts to
the RUN mode.
16
Open the front panel and locate the
RESET switch. Press to reset the
System-10.
When polled, the System-10
will automatically begin
to communicate with the
network.
RESET is located along the top
of the heat computer board.
(See appendix page A-9.)
4.5.1 Application Number
The application number is assigned to the BTU meter based on the calibration parameters
supplied at the time the BTU meter was calibrated. If the system parameters change,
please contact ONICON for assistance in determining the correct application number.
TABLE OF STANDARD SYSTEM-10-P1 APPLICATION NUMBERS
Application
Number
Point 3 Displayed
Energy Rate
Points 9, 10
Displayed Energy
Total
Points 11, 12
Displayed Flow
Total
Point 4
Displayed Flow
Rate
Points 5, 6, 7
Displayed
Temperature
1998 BTU/HR x 1,000 BTU x 1,000 GAL x 10 GPM x 1 DEG F
1997 BTU/HR x 1,000 BTU x 10,000 GAL x 10 GPM x 1 DEG F
1996 BTU/HR x 1,000 BTU x 10,000 GAL x 100 GPM x 1 DEG F
1995 BTU/HR x 1,000 BTU x 10,000 GAL x 1,000 GPM x 1 DEG F
1994 BTU/HR x 1,000 BTU x 100,000 GAL x 100 GPM x 1 DEG F
1993 BTU/HR x 1,000 BTU x 100,000 GAL x 1,000 GPM x 1 DEG F
1992 BTU/HR x 1,000,000 BTU x 100,000 GAL x 1,000 GPM x 1 DEG F
1991 BTU/HR x 1,000,000 BTU x 100,000 GAL x 10,000 GPM x 1 DEG F
1990 BTU/HR x 1,000,000 BTU x 1,000,000 GAL x 1,000 GPM x 1 DEG F
1989 BTU/HR x 1,000,000 BTU x 1,000,000 GAL x 10,000 GPM x 1 DEG F
1988 BTU/HR x 1,000,000 BTU x 1,000,000 GAL x 10,000 GPM x 10 DEG F
1987 BTU/HR x 1,000 TON-HRS x 1 GAL x 100 GPM x 1 DEG F
1986 BTU/HR x 1,000 TON-HRS x 1 GAL x 1,000 GPM x 1 DEG F
1985 BTU/HR x 1,000 TON-HRS x 10 GAL x 1,000 GPM x 1 DEG F
1984 BTU/HR x 1,000,000 TON-HRS x 10 GAL x 1,000 GPM x 1 DEG F