Onicon System-10 P1 Manual do Utilizador Página 14

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 67
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 13
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
System-10-P1 Manual 10/14 - 0656-9 / 18320 Page 14
3.2.4 Flow Meter Installation
Determine which pipe (supply or return) has the longer unobstructed straight run. Install
the ow meter in the longest straight pipe run available. One temperature sensor can be
installed ve diameters downstream of the ow meter leaving enough clearance to remove
either sensor from the pipe without interference from the other sensor.
Also refer to the installation manual and/or other documentation that is provided with
your ONICON ow meter.
For F-1300 series inline turbine ow meters, refer to the documentation that is provided
with the ow meter.
ONICON TEMPERATURE SENSOR
TEMPERATURE SENSOR INSTALLED IN THERMOWELL
Vista de página 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 66 67

Comentários a estes Manuais

Sem comentários