4.3 START-UP & COMMISSIONING WORKSHEET
Please read all installation instructions carefully prior to proceeding with these steps. Use the
following worksheet for checking off the commissioning steps and recording measured values.
STEP TEST/MEASUREMENT S/N: S/N: S/N: S/N:
1. Meter location:
2. Conrm pipe size:
3. Conrm orientation:
4. Control system
programming:
5. Match display
serial number
(S/N) if ordered:
6. Signal connections
veried:
7. Supply voltage veried:
8. Connect power:
The following steps require ow in the pipe. Flow signal readings should be taken while holding the ow rate
constant, if possible. Otherwise, take the various output readings as quickly as possilbe.
9. Analog or pulse output(s)
4 - 20 mA signal:
Scaled output interval:
Calculated ow rate:
__________mA
____________
_______SCFH
__________mA
____________
_______SCFH
__________mA
____________
_______SCFH
__________mA
____________
_______SCFH
10. Flow rate displayed by con-
trol system: _______SCFH _______SCFH _______SCFH _______SCFH