3.3 INSERTION METER MECHANICAL INSTALLATION
ONICON Insertion Turbine Flow Meters employ a hot tap adapter design that allows for
insertion and removal, when necessary, without interrupting ow and draining the pipe. To take
advantage of this feature, the ow meter must be installed through an isolation valve. The
installation must also allow for sufcient overhead clearance to fully extract the meter, and a full
1” opening in the pipe wall is required to clear the sensor head and allow for insertion. Make sure
that your valves and ttings are full port and at least 1” in actual internal diameter.
CAUTION
ONICON insertion style ow meters must be installed through a valve assembly. Failure to do so
negates the ability to remove the meter without shutting down ow and draining the system. It will
also result in an excessive amount of stem protruding from the pipe. Excessive stem lengths
unneccessarily expose the meter to incidental damage.
!
IMPORTANT NOTE
Flow meters installed through oversized access holes will be subjected to undesirable turbulence
that may affect the accuracy of the meter.
!
i
!
Typically
30" - 40"
depending on
pipe size and
height of valve
assembly.
CLEARANCE
REQUIRED
FOR INSTALLATION
Minimum Hole Size = 1"
Must be centered
Standard Installation
Kit for Steel Pipe
1" Full port ball valve
1" Close nipple
1" Branch outlet
1¼" for
hot tap
NOTE: Use stainless steel or brass
close nipple only.
23”- 36”