System-30 BTU Measurement System MODBUS RTU RS485 04/14 - 0583-1 / 18345 Page 10
3.2 MECHANICAL INSTALLATION
3.2.1 Main Unit Installation
ISOLATION VALVE
Normally Open
ISOLATION VALVE
Normally Open
BYPASS VALVE
Normally Closed
20"
5"
CHILLED WATER
SUPPLY
Y Strainer Upstream
Of Flow Meter
CHILLED WATER
RETURN
CONTROL SYSTEM
BACnet MS/TP
NETWORK
24 VAC POWER
FAN COIL UNIT
OR
AIR HANDLING UNIT
RETURN TEMP
FLOW
DIAGNOSTIC
LED’S
CONTROL SYSTEM
MODBUS RTU
NETWORK
24V AC/DC
!
CAUTION
Before you attempt to use the BTU measurement system, isolate the main unit, open the bypass
and ush the entire system so that it is free of ux, solder, pipe and tube cuttings and any other
free moving particles.
Installing the meter body
1. Make sure the unions are free of nicks or scratches on either end of the ow
meter body and on the process connections.
2. Spray the union faces with a silicone spray or apply a thin coat of beeswax to enhance
seating. Do not use paste thread sealant on union faces.
3. Orient the ow arrow on the meter with the direction of ow.
4. Recommended torques for union seal: 70 ft/lbs minimum
5. Make sure alignment of pipe does not put lateral stress on either joint.
Process
Connection
Process
Connection
Unions