Onicon System-30 BTU Manual do Utilizador Página 10

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 31
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 9
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-30 BTU Measurement System Manual 05/14 - 0667-2 / 18335 Page 10
3.2 MECHANICAL INSTALLATION
3.2.1 Main Unit Installation
TYPICAL SYSTEM-30 INSTALLATION
!
CAUTION
Before you attempt to use the BTU measurement system, isolate the main unit, open the bypass
and ush the entire system so that it is free of ux, solder, pipe and tube cuttings and any other
free moving particles.
Installing the meter body
1. Make sure the unions are free of nicks or scratches on either end of the ow
meter body and on the process connections.
2. Spray the union faces with a silicone spray or apply a thin coat of beeswax to enhance
seating. Do not use paste thread sealant on union faces.
3. Orient the ow arrow on the meter with the direction of ow.
4. Recommended torques for union seal: 70 ft/lbs minimum
5. Make sure alignment of pipe does not put lateral stress on either joint.
Process
Connection
Process
Connection
Unions
Vista de página 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 30 31

Comentários a estes Manuais

Sem comentários