System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322 Page 12
SECTION 2.0: POINT FILE (.ddl)
2.1 ddl OR POINT FILE
The System-10 BTU Meter operates in one of three operating modes: single, dual or bi-directional.
The dual and bi-directional modes utilize the same .ddl les. The tables below contain point
information for each of the operating modes.
The .ddl le contains the information that identies the device to the N2 supervisory controller.
It also species the variables that are available to be transmitted to and from the device on the
network.
The tables below contains .ddl le information
2.1.1 Single Mode Point Information
In single mode operation, only one register accumulates energy and one register
accumulates volume.
NPT
1
NPA
2
UNITS POINT DESCRIPTION RANGE/VALUE
AI 1
Selectable
(See Energy Rate
Table)
Energy Rate 0 - 999,999
AI 2
Selectable
(See Volume Rate
Table)
Volume Rate 0 - 999,999
AI 3
Deg F Supply Temperature 0.0 Deg F - 500.0 Deg F
AI 4
Deg F Return Temperature 0.0 Deg F - 500.0 Deg F
BI 1
None Dual Mode Status Indicator
- Heating (supply > return)
- Cooling (supply < return)
OR
- Forward ow
- Reverse ow
(Refer to Section 3.3.3 of
System-10 manual for ow
direction information.)
0 - Heating
1 - Cooling
0 - Forward
1 - Reverse
ADF 1
Selectable
(See Energy Total
Table)
Mode 1 Energy Total 0 – 999,999
ADF 2
Selectable
(See Volume Total
Table)
Mode 1 Volume Total 0 – 999,999
ADF 5
User Dened Auxiliary Pulse Input Sum (Di3) 0 – 999,999
BO 1
None Reset (Zero)
Energy Total, ADF-1
OVERRIDE
Binary Output,
Object 1 - ON