SECTION 2.0: POINT FILE (.ddl)
2.1 ddl OR POINT FILE
The System-10 BTU Meter operates in one of three operating modes: single, dual or bi-directional.
The dual and bi-directional modes utilize the same .ddl les. The tables below contain point
information for each of the operating modes.
The .ddl le contains the information that identies the device to the N2 supervisory controller.
It also species the variables that are available to be transmitted to and from the device on the
network.
The tables below contains .ddl le information
2.1.1 Single Mode Point Information
In single mode operation, only one register accumulates energy and one register
accumulates volume.
NPT
1
NPA
2
UNITS POINT DESCRIPTION RANGE/VALUE
AI 1
Selectable
(See Energy Rate
Table)
Energy Rate 0 - 999,999
AI 2
Selectable
(See Volume Rate
Table)
Volume Rate 0 - 999,999
AI 3
Deg F Supply Temperature 0.0 Deg F - 500.0 Deg F
AI 4
Deg F Return Temperature 0.0 Deg F - 500.0 Deg F
BI 1
None Dual Mode Status Indicator
- Heating (supply > return)
- Cooling (supply < return)
OR
- Forward ow
- Reverse ow
(Refer to Section 3.3.3 of
System-10 manual for ow
direction information.)
0 - Heating
1 - Cooling
0 - Forward
1 - Reverse
ADF 1
Selectable
(See Energy Total
Table)
Mode 1 Energy Total 0 – 999,999
ADF 2
Selectable
(See Volume Total
Table)
Mode 1 Volume Total 0 – 999,999
ADF 5
User Dened Auxiliary Pulse Input Sum (Di3) 0 – 999,999
BO 1
None Reset (Zero)
Energy Total, ADF-1
OVERRIDE
Binary Output,
Object 1 - ON