Onicon System-10 MODBUS Manual do Utilizador Página 11

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 35
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 10
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-MOD Network Interface Installation Guide 05/14 - 0653-10 / 18321 Page 11
1.5 RS485 BAUD RATE, BIASING AND TERMINATION
1.5.1 Baud Rate
Every ONICON System-10 is individually programmed at the factory with application
specic data provided by the customer during the process of ordering the Btu meter. This
normally includes the Baud rate setting. If the Baud rate was provided, the Btu meter will
be congured to operate at the specied rate. The available Baud rate settings are listed in
the table below.
If the Baud rate setting was not provided to ONICON, the Btu meter will be congured
to 9600.
The Baud rate setting can be manually changed in the eld. The drawing and table
below show the Baud rate dipswitch settings.
BAUD Rate B1 B2 B3 B4
9600 OFF OFF OFF OFF
1200 ON OFF OFF OFF
2400 ON ON OFF OFF
4800 ON OFF ON OFF
9600 ON ON ON OFF
19200 ON OFF OFF ON
38400 ON ON OFF ON
57600 ON OFF ON ON
115200 ON ON ON ON
Baud Rate Dip Switches
ON
Vista de página 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 34 35

Comentários a estes Manuais

Sem comentários