1.5 RS485 BAUD RATE, BIASING AND TERMINATION
1.5.1 Baud Rate
Every ONICON System-10 is individually programmed at the factory with application
specic data provided by the customer during the process of ordering the Btu meter. This
normally includes the Baud rate setting. If the Baud rate was provided, the Btu meter will
be congured to operate at the specied rate. The available Baud rate settings are listed in
the table below.
If the Baud rate setting was not provided to ONICON, the Btu meter will be congured
to 9600.
The Baud rate setting can be manually changed in the eld. The drawing and table
below show the Baud rate dipswitch settings.
BAUD Rate B1 B2 B3 B4
9600 OFF OFF OFF OFF
1200 ON OFF OFF OFF
2400 ON ON OFF OFF
4800 ON OFF ON OFF
9600 ON ON ON OFF
19200 ON OFF OFF ON
38400 ON ON OFF ON
57600 ON OFF ON ON
115200 ON ON ON ON
Baud Rate Dip Switches